KODAK
INVERTER GUIDE
+ SETTINGS + COMMUNICATION + TROUBLESHOOTING
The Kodak Off-Grid inverters are fully compatible with the Hubble range of batteries.
The following field guide will assist with the correct battery settings you should use.
​
For further detailed information ensure you read the manual of the supplied battery regarding setup and installation instructions.
​
WARNING
​
Working with high-voltage systems is dangerous. Do not attempt to modify your inverter and battery setup unless you are certain you understand the risk. Speak to a qualified electrician if you are unsure.
INVERTER EXAMPLE
INVERTER SETTINGS
Model | Voltage | Equalised | Float | Cutoff | Charge Amps | Max Discharge Current |
---|---|---|---|---|---|---|
S-SERIES | 12V | 14 | 14 | 12 | 30A | 100A |
X-100 | 48V | 52.8 | 52.8 | 44 | 30A | 100A |
X-101 | 48V | 53.8 | 53.8 | 44 | 30A | 100A |
X-200 | 36V | 41.5 | 41.5 | 34 | 30A | 100A |
AM-2 | 48V | 53.8 | 53.8 | 44 | 30A | 100A |
AM-3 | 48V | 53.8 | 53.8 | 44 | 20A | 50A |
AM-4 | 24V | 29 | 28.5 | 22 | 30A | 100A |
AM-5 | 48V | 55.2 | 55.2 | 47 | 30A | 100A |
AM-10 | 48V | 55.2 | 55.2 | 47 | 60A | 150A |
BLADE | 48V | 55.2 | 55.2 | 47 | 50A | 200A |
PIN LAYOUTS & CLOUDLINK
PLEASE NOTE
Axpert type inverters require a Cloudlink to access full CAN-BUS communication with a Hubble Energy battery, it is however not required, and the system will be functional on user defined voltage control.
CLOUDLINK
The Cloudlink will connect to a Kodak Inverter via:
Cloudlink’s (Serial/RJ12 Port) to the Kodak Inverter (RS232 Port)
(Black Cable) - Serial/RJ12 to RJ45 (450mm) cable.
The Cloudlink will connect to the Battery via:
Cloudlink’s (CAN Port) to the Battery (CAN Port)
(Blue Cable) - Standard RJ45 to RJ45 (1500mm) cable.
RJ45 PIN LAYOUTS
Ensure that the clip is pointed away from you when counting the pins.
PIN | X-101/AM-4/AM-2 | AM-5/AM-10 |
---|---|---|
1 | - | - |
2 | GROUND | - |
3 | - | - |
4 | CANH | CANH |
5 | CANL | CANL |
6 | - | |
7 | - | - |
8 | - | - |
2, 4 & 5 Pin Layout image reference seen below: (Blue Cable)
4 & 5 Pin Layout image reference seen below: (Blue Cable - Modified)
HUBBLE DIP SWITCH SETTINGS
FOR MULTIPLE BATTERY INSTALLATION
For correct setup and communication, each battery needs a unique serial address to communicate. If you are only using one battery in your setup, consider this the master battery and ensure you set it to address 1.
AM-2, AM- 4 & BLADE DIP SWITCHES
ADDRESS | SWITCH POSITIONS | SWITCH POSITIONS | SWITCH POSITIONS | SWITCH POSITIONS |
---|---|---|---|---|
#1 | #2 | #3 | #4 | |
1 | ON | OFF | OFF | OFF |
2 | OFF | ON | OFF | OFF |
3 | ON | ON | OFF | OFF |
4 | OFF | OFF | ON | OFF |
5 | ON | OFF | ON | OFF |
6 | OFF | ON | ON | OFF |
7 | ON | ON | ON | OFF |
8 | OFF | OFF | OFF | ON |
9 | ON | OFF | OFF | ON |
10 | OFF | ON | OFF | ON |
11 | ON | ON | OFF | ON |
12 | OFF | OFF | ON | ON |
13 | ON | OFF | ON | ON |
14 | OFF | ON | ON | ON |
15 | ON | ON | ON | ON |
AM-5 & AM-10 DIP SWITCHES (4-DIP VERSION)
ADDRESS | SWITCH POSITIONS | SWITCH POSITIONS | SWITCH POSITIONS | SWITCH POSITIONS |
---|---|---|---|---|
#1 | #2 | #3 | #4 | |
1 | OFF | OFF | OFF | OFF |
2 | ON | OFF | OFF | OFF |
3 | OFF | ON | OFF | OFF |
4 | ON | ON | OFF | OFF |
5 | OFF | OFF | ON | OFF |
6 | ON | OFF | ON | OFF |
7 | OFF | ON | ON | OFF |
8 | ON | ON | ON | OFF |
9 | OFF | OFF | OFF | ON |
10 | ON | OFF | OFF | ON |
11 | OFF | ON | OFF | ON |
12 | ON | ON | OFF | ON |
13 | OFF | OFF | ON | ON |
14 | OFF | ON | ON | ON |
15 | ON | ON | ON | ON |
AM-10 (8-DIP VERSION)
ADDRESS | SWITCH POSITIONS | SWITCH SETTINGS | SWITCH SETTINGS | SWITCH SETTINGS | SWITCH SETTINGS | SWITCH SETTINGS | SWITCH SETTINGS |
---|---|---|---|---|---|---|---|
#1 | #2 | #3 | #4 | #5 | #6 | Mark (#7 & #8) | |
0 | ON | ON | OFF | OFF | OFF | OFF | Mastery Battery/Enable CAN BUS Port - ON |
1 | OFF | OFF | OFF | OFF | OFF | OFF | Slave 2 - OFF |
2 | OFF | ON | OFF | OFF | OFF | OFF | Slave 3 - OFF |
3 | OFF | OFF | ON | OFF | OFF | OFF | Slave 4 - OFF |
4 | OFF | ON | ON | OFF | OFF | OFF | Slave 5 - OFF |
5 | OFF | OFF | OFF | ON | OFF | OFF | Slave 6 - OFF |
6 | OFF | ON | OFF | ON | OFF | OFF | Slave 7 - OFF |
7 | OFF | OFF | ON | ON | OFF | OFF | Slave 8 - OFF |
8 | OFF | ON | ON | ON | OFF | OFF | Slave 9 - OFF |
9 | OFF | OFF | OFF | OFF | ON | OFF | Slave 10 - OFF |
10 | OFF | ON | OFF | OFF | ON | OFF | Slave 11 - OFF |
11 | OFF | OFF | ON | OFF | ON | OFF | Slave 12 - OFF |
12 | OFF | ON | ON | OFF | ON | OFF | Slave 13 - OFF |
13 | OFF | OFF | OFF | ON | ON | OFF | Slave 14 - OFF |
14 | OFF | ON | OFF | ON | ON | OFF | Slave 15 - OFF |