INVERTER SETTINGS

Model
Voltage
Equalised
Float
Cutoff
Charge Amps
Max Discharge Current
S-SERIES
12V
14
14
12
30A
100A
X-100
48V
52.8
52.8
44
30A
100A
X-101
48V
53.8
53.8
44
30A
100A
X-200
36V
41.5
41.5
34
30A
100A
AM-2
48V
53.8
53.8
44
30A
100A
AM-3
48V
53.8
53.8
44
20A
50A
AM-4
24V
29
28.5
22
30A
100A
AM-5
48V
55.2
55.2
47
30A
100A
AM-10
48V
55.2
55.2
47
60A
150A
BLADE
48V
55.2
55.2
47
50A
200A

Setting up a Hubble with a MLT Powerstart is incredibly easy.
Simply plug in the Hubble master battery into the CAN bus port of the MLT Powerstart.

​

This will automatically setup the below values.

PIN LAYOUTS & CLOUDLINK

PLEASE NOTE

Axpert type inverters require a Cloudlink to access full CAN-BUS communication with a Hubble Energy battery, it is however not required, and the system will be functional on user defined voltage control.

CLOUDLINK

The Cloudlink will connect to a Microcare Inverter via:

 

Cloudlink’s (Serial/RJ12 Port) to the Microcare Inverter (RS232 Port) 

(Black Cable) - Serial/RJ12 to RJ45 (450mm) cable.

 

The Cloudlink will connect to the Battery via:

 

Cloudlink’s (CAN Port) to the Battery (CAN Port) 

(Blue Cable) - Standard RJ45 to RJ45 (1500mm) cable.

RJ45 PIN LAYOUTS

Ensure that the clip is pointed away from you when counting the pins.

PIN
X-101/AM-4/AM-2
AM-5/AM-10
1
-
-
2
GROUND
-
3
-
-
4
CANH
CANH
5
CANL
CANL
6
-
7
-
-
8
-
-

2, 4 & 5 Pin Layout image reference seen below: (Blue Cable)

Microcare Inverter setup guide

4 & 5 Pin Layout image reference seen below: (Blue Cable - Modified)

Microcare Inverter setup guide

HUBBLE DIP SWITCH SETTINGS

FOR MULTIPLE BATTERY INSTALLATION

For correct setup and communication, each battery needs a unique serial address to communicate. If you are only using one battery in your setup, consider this the master battery and ensure you set it to address 1.

AM-2, AM- 4 & BLADE DIP SWITCHES

ADDRESS
SWITCH POSITIONS
SWITCH POSITIONS
SWITCH POSITIONS
SWITCH POSITIONS
#1
#2
#3
#4
1
ON
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
3
ON
ON
OFF
OFF
4
OFF
OFF
ON
OFF
5
ON
OFF
ON
OFF
6
OFF
ON
ON
OFF
7
ON
ON
ON
OFF
8
OFF
OFF
OFF
ON
9
ON
OFF
OFF
ON
10
OFF
ON
OFF
ON
11
ON
ON
OFF
ON
12
OFF
OFF
ON
ON
13
ON
OFF
ON
ON
14
OFF
ON
ON
ON
15
ON
ON
ON
ON

AM-5 & AM-10 DIP SWITCHES (4-DIP VERSION)

ADDRESS
SWITCH POSITIONS
SWITCH POSITIONS
SWITCH POSITIONS
SWITCH POSITIONS
#1
#2
#3
#4
1
OFF
OFF
OFF
OFF
2
ON
OFF
OFF
OFF
3
OFF
ON
OFF
OFF
4
ON
ON
OFF
OFF
5
OFF
OFF
ON
OFF
6
ON
OFF
ON
OFF
7
OFF
ON
ON
OFF
8
ON
ON
ON
OFF
9
OFF
OFF
OFF
ON
10
ON
OFF
OFF
ON
11
OFF
ON
OFF
ON
12
ON
ON
OFF
ON
13
OFF
OFF
ON
ON
14
OFF
ON
ON
ON
15
ON
ON
ON
ON

AM-10 (8-DIP VERSION)

ADDRESS
SWITCH POSITIONS
SWITCH POSITIONS
SWITCH POSITIONS
SWITCH POSITIONS
SWITCH POSITIONS
SWITCH POSITIONS
SWITCH POSITIONS
#1
#2
#3
#4
#5
#6
Mark (#7 & #8)
0
ON
ON
OFF
OFF
OFF
OFF
Mastery Battery/Enable CAN BUS Port - ON
1
OFF
OFF
OFF
OFF
OFF
OFF
Slave 2 - OFF
2
OFF
ON
OFF
OFF
OFF
OFF
Slave 3 - OFF
3
OFF
OFF
ON
OFF
OFF
OFF
Slave 4 - OFF
4
OFF
ON
ON
OFF
OFF
OFF
Slave 5 - OFF
5
OFF
OFF
OFF
ON
OFF
OFF
Slave 6 - OFF
6
OFF
ON
OFF
ON
OFF
OFF
Slave 7 - OFF
7
OFF
OFF
ON
ON
OFF
OFF
Slave 8 - OFF
8
OFF
ON
ON
ON
OFF
OFF
Slave 9 - OFF
9
OFF
OFF
OFF
OFF
ON
OFF
Slave 10 - OFF
10
OFF
ON
OFF
OFF
ON
OFF
Slave 11 - OFF
11
OFF
OFF
ON
OFF
ON
OFF
Slave 12 - OFF
12
OFF
ON
ON
OFF
ON
OFF
Slave 13 - OFF
13
OFF
OFF
OFF
ON
ON
OFF
Slave 14 - OFF
14
OFF
ON
OFF
ON
ON
OFF
Slave 15 - OFF

FREQUENTLY ASKED QUESTIONS

How do you set up multiple batteries?

You will have to set dip switch settings per battery to give them a unique address. You also must connect the included RJ45 battery link cables into the "Battery Link" port of each battery. Ensure your master battery dip switch 1 is on, 2,3,4 is OFF.  Only the master battery CAN Bus will be enabled. You can then connect the Hubble Cloudlink into the CAN port of the master battery for communications to work.

Do I have to use the communication battery link cables if I don’t want to monitor or have communications?

Yes.

bottom of page